Environmental Health & SafetyPotable (Drinking) WaterSan Diego State University Appendix C: Emergency Water Main Disinfection Procedures When repairs require that mains be opened and depressurized under emergency conditions such as a break or other physical failure of the pipeline, the necessity to restore water service as soon as possible prevents complete compliance with the routine main disinfection procedures of AWWA Standard §C651-92. Alternate disinfection procedures under such conditions were described in detail in an article by R. Scott Yoo, “Procedures for Emergency Disinfection of Mains,” Opflow, Vol 12, No. 1, (January 1986). The following recommended procedures are based in part on this article:
The swabbing method, however, should not be utilized where there is a potential for significant contamination of the main (for example, sewage is detected in the trench during repairs).
Preliminary Steps — Both methods require the repaired section of main be isolated from the distribution system. This will require the shut off of all service connections along the section of main to be disinfected. Temporary connections for filling the main with water as well as a method of flushing the main through a hydrant or other temporary outlet must be provided. The isolated section of main must be initially flushed to remove dirty water, debris, and air. Hypochlorite Injection — In the hypochlorite injection method, liquid sodium hypochlorite is injected into the flowing main by means of a chemical-feed pump to achieve a high chlorine residual (see Figure 1). The initial required chlorine dose is 300 mg/L, verified by measuring chlorine residuals in the flushed water through an outlet in the end of the section. The minimum amount of hypochlorite solution, which is required to treat one pipe volume with an initial chlorine dose of 300 mg/L, can be determined using the following table: Table 7 includes the minimum volumes of sodium hypochlorite solution (5 and 12.5‰-available chlorine) necessary to achieve an initial chlorine dosage of 300 mg/L in 100 feet of main. Volumes in excess of the table values will be necessary because pumping must continue until the minimum chlorine dose is verified at the flushing outlet. Addition of Premixed Solution — An alternate method is the preparation of a premixed chlorine-water solution in sufficient volume to completely fill the repaired section of main. A hypochlorite compound is added to potable water in a tanker truck or other large container to form a solution with at least 300 mg/L free chlorine (see Table 7). The solution from the tanker truck or large container is pumped into the repaired section of main until the main is full, as indicated by a discharge through a hydrant or other outlet at the other end of the section. Minimum Contact Period — The minimum contact period for an initial chlorine dose of 300 mg/L is 15 minutes. After the minimum 15-minute contact period, a chlorine residual of at least 100 mg/L should be verified. Lower initial chlorine doses may be used for longer contact periods (e.g., 100 mg/L initial chlorine dose with a 3-hour contact time). Final Steps — The heavily chlorinated water is flushed from the main until the chlorine residual is reduced to the level normally present in water supplied to the area. Consideration should be given to the collection of bacteriological samples after disinfection is completed to provide a record of the effectiveness of the procedures where repairs were conducted under conditions that posed a threat of significant contamination. |
|
This page last updated September 24, 2008 |
||